mechanisms) and bilateral agreements between producers and consumers need to be coordinated. Eventually, energy producers offer their production capacity and get it awarded in, with a price assigned per MW to the different generation sources.

      Technical aspects of the different conventional generation sources are taken into consideration together with the economic mechanisms. Their different constraints (e.g., costs, speed of startup and shutdown, capacity factor, forecast of day availability) determine unit commitments [11]. These are assignments of a production rate and temporal slot some time in advance of the real need. To cope with unexpected contingencies, the reserves (i.e., the “back‐up” generation units) are planned as well.

      Frequency stability is a key aspect of power system operation. It starts in the Generation segment. Traditional production of electricity (hydro, fuel, nuclear) involves mechanical elements (e.g., water, steam, or gas flowing through a turbine) and has an effect on the rotational speed of the turbine that consequently determines the exact frequency of the electricity signal. If rotational speed is higher, frequency is higher too. Loads also affect system frequency: when load is heavy, the turbine will tend to rotate more slowly, and the output frequency will be lower. This effect needs to be compensated on the generator side (with the mechanical resources) to keep the frequency as close as possible to the 50 or 60 Hz nominal value.

      Voltage levels are the other key aspect that needs to be controlled. Loads in the system exhibit a reactive behavior and, if the consumption of reactive power is excessive, the generated output power will not be efficiently used. The grid (Transmission and Distribution segments) takes care of compensating loads to keep reactive consumption low and maximizes the real power flowing in the system. As a last resource, generators may need to act.

      Distribution systems are the most significant in terms of territory coverage and have a fundamental role in supply availability and quality control. Distribution operations take care of the control and the voltage regulation (i.e., LV levels within limits in both the unloaded and full‐load conditions), power factor (i.e., the reactive part of the load), harmonics (degradation of the waveform frequency, more common due to the growing presence of solid‐state switching devices in the grid), and voltage unbalance among phases in multiphase systems. Literature [4] specifically identifies concepts such as supply outages (supply interruptions of different duration), voltage drops (dips in supply voltage), overvoltage (voltage increases caused by network events), voltage wave harmonics (deviations from the fundamental frequency), and flicker (low‐frequency fluctuations in voltage amplitude frequency).

      1.2.4 The Grid Assets

      Grid assets are the elements of the electric power system. This section will focus on the network part of it, i.e., Transmission and Distribution segments.

      All the network elements are important not only because they are the elements making the grid work but also because they are the elements to be controlled, the ones needing telecommunication services, and the ones that can be used to support the means to develop telecommunication networks (e.g., optical fiber cables on the power lines).

      1.2.4.1 Substations

      Substations are the grid nodes where voltage level is transformed. PSs transform voltage from HV to MV and SSs from MV to LV. Both PSs and SSs use transformers for this purpose, and as voltage is reduced, current is increased. Voltage transformation takes place in several stages and at several substations in sequence. These substations are connected through power lines.

      Other than the transformer as the main component of a substation, substations consist of a complex set of circuit breaking, and control equipment arranged to direct the flow of electric power. Substations perform several functions, namely, safety (isolating parts of the system in case an electric fault occurs), operation (minimization of energy losses; separation of parts of the network when maintenance or network upgrades are needed), and interconnection (if different electric networks with diverse voltages need to be connected).

Photos depict primary substation examples.

      The number of SSs in the grid exceeds the number of PSs with a factor than can be in excess of 100. Due to their relevance in the evolution into the Smart Grid, it is worth describing the structure of an SS, from its MV input to its LV output:

       MV lines. These are the power lines carrying voltages and currents that originate from PSs.

       Switchgear or MV panels. These are the interfaces between MV lines and the transformer or transformers. The switchgear protects the transformer and allows the interconnection of MV feeders. Switchgear maybe open‐air or encapsulated air‐insulated (old versions) or encapsulated with a gaseous dielectric medium (usually sulfur hexafluoride, SF6).

       Transformer. The device that steps down the voltage from MV levels to LV.

       LV panel. The element located beyond the transformer, connected to its secondary winding, and distributing the electric power in a number of LV feeders that will eventually reach Consumption Points. It is usually a large single panel or frame composed of four horizontal bars where the LV feeders are connected (for the three phases and the neutral). The LV switchboard usually is fitted with switches, overcurrent, and other protective elements.Figure 1.6 Different types of secondary substations.

       LV feeders. These are the power lines supporting specific voltages and currents that deliver electric energy to customers. Usually several LV lines come out of a single